SPECIFICATION
ModelDR-240-24
OUTPUTDC VOLTAGE24V
RATED CURRENT10A
CURRENT RANGE0 ~ 10A
RATED POWER240W
RIPPLE&NOISE(Max)150mVp-p
VOLTAGE ADJ.RANGE24 ~ 30V
VOLTAGE TOLERANCE±1.0%
LINE REGULATION±0.5%
LOAD REGULATION±1.0%
SETUP,RISE TIME500ms、30ms/230VAC 1000ms,30ms/115VAC(full load)
INPUTVOLTAGE RANGE85~264VAC , 120~370VD
FREQUENCY RANGE47~63Hz
EFFICIENCY(Typ.)0.85
AC CURRENT(Typ.)0.7A/115VAC 40A/230VAC
INRUSH CURRENT(Typ.)COLDSTART: 60A/230V
LEAKAGE CURRENT<1mA/240VAC
PROTECTIONOVER
LOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER
VOLTAGE
28.4~32.4V
Protection type : Shut down o/p voltage, re-power on to recover
ENVIRONMENTWORKING TEMP-10 ~ +60°C
WORKING HUMIDITY20~90%RH
STORAGETEMP.,HUMIDITY-20 ~ +85°C, 20 ~ 90% RH
VIBRATIONComponent : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETYSAFETY STANDARDSCE,GB4943.1safety standard
WITHSTAND VOLTAGEI/P-O/P:1.5KVAC 1minute I/P-FG:1.5KVAC 1minute O/P-PG:0.5KVAC 1minute
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100MOhms/500VDC
EMC EMISSIONEN61000-3-2:2014/EN61000-3-3:2013
EMC IMMUNITYEN 55032:2015/EN55035:2017/60950-1
OTHERSMTBF≥327.9K hrs MIL-HDBK-217F(25°C)
DIMENSION125.2*100*125.2mm