SPECIFICATION
ModelLRS-200-12
OUTPUTDC VOLTAGE12V
RATED CURRENT17A
CURRENT RANGE0 ~ 17A
RATED POWER204W
RIPPLE&NOISE(Max)150mVp-p
VOLTAGE ADJ.RANGE10.2~ 13.8V
VOLTAGE TOLERANCE±1.5%
LINE REGULATION±0.5%
LOAD REGULATION±1.0%
SETUP,RISE TIME1500ms, 50ms/230VAC1500ms, 50ms/115VAC(fullload)
HOLD UP TIME(Typ.)16ms/230VAC12ms/115VAC (fullload)
INPUTVOLTAGE RANGE85 ~ 132VAC/170 ~ 264VACselected by switch 240~370VDC(switch on 230VAC)
FREQUENCY RANGE47~63Hz
EFFICIENCY(Typ.)0.87
AC CURRENT(Typ.)4A/115VAC 2.2A/230VAC
INRUSH CURRENT(Typ.)COLD START 60A/230VAC 60A/115VAC
LEAKAGE CURRENT<2mA / 240VAC
PROTECTIONOVER
LOAD
110~140% rated output power
12~36V Hiccup mode, recovers automatically after fault condition is removed
OVER
VOLTAGE
13.8~16.2V
Protectiontype:Shut down o/p voltage, re-power on to recover
ENVIRONMENTWORKING TEMP-20~70℃(Refer to "derating curve")
WORKING HUMIDITY20~90%RH non-condensing
STORAGETEMP.,HUMIDITY-45 ~ +85°C, 20% ~ 95% RH non-condensing
TEMP.COEFFICIENT±0.03%/°C (0 ~ 50°C)
VIBRATION10 ~ 500Hz, 2G10min/1cycle,60min.eachX、Y、Zaxes
SAFETYSAFETY STANDARDSGB4943.1, EN60950.1APPROVED
WITHSTAND VOLTAGEI/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCEI/P-O/P, I/P-FG, O/P-FG:100MOhms / 500VDC / 25°C/ 70% RH
EMC EMISSIONCompliance toEN61000-3-2:2014/EN61000-3-3:2013
EMC IMMUNITYCompliance toEN55032:2015/EN55035:2017/60950-1
OTHERSMTBF≥347.5 hrs MIL-HDBK-217F(25°C)
DIMENSION215*115*30mm (L*W*H)