Type and Specification
Comply with the standardIEC/EN 60898-1
ModelPH8H2
Poles1P+N
Rated current(A) In6-40
Rated frequency(Hz)50/60
Rated working voltage(V) Ue230~
Rated insulated voltage(V) Ui400
Impulse withstand voltage(kV) Uimp4
Rated short-circuit breaking capacity(KA) Icn6
Instantaneous tripping typeB,C,D
Maximum working voltage Umax240
Dielectric test voltage(KV)2
Service life Mechanical Standard value10000
(O-C) Electrical Standard value4000
Shunt release(SHT)
Undervoltage release(UVT)
Auxiliary contact(AUX)
Alarm contact(ALT)
Contact position indicator
Fault indication-
Ambient temperature(with daily averages35℃)-5℃~+40℃
Protection degreeALL SidesIP40
Connection TerminalIP20
Wire(mm²)1-10
MountingCable
Pollution degree2
Reference temperature for setting of thermal element(℃)30
Storage temperature(℃)-25℃~+70℃
Tightening torque2.5
ConnectionTop and Bottom
Dimensions(mm)
(WxHxL)
a(1P/2P/3P/4P)17.5(1P+N)
b(1P/2P/3P/4P)87(1P+N)
c(1P/2P/3P/4P)77.5(1P+N)
Weight(kg)1P0.13(1P+N)
■Default □ Optional -None

 

PN8H mini circuit breaker is used for protection against overload and short circuit in the circuit of 50/60Hz, rated voltage 230V, rated current up to 40A, It also can be used for non-frequent on-and-off switching operation under normal circumstance.In compliance with IEC/EN60898-11P+N structure,17.5mm Volume.With indicator function in the contact position.Bilateral busbar wiring capabilities to adapt to the wider use of premises.Maximum connecting ability of 16mm2,wiring torque 2.5N m, applicable to a variety of installing equipments,wiring stronger.Protection class:IP20